| AWAIV with Version 4.2.5 Software | ||||||||||||
|
My
Baker Instrument Company Advanced Winding Analyzer IV does not
stabilize the resistance test lead readings on certain very large
electric motors. The error message that comes back is:
“Resistance
measurements are unstable. Check for noise sources nearby (welders,
VFD’s, etc) or a free wheeling rotor”
“Instrument
detecting excessive electrical noise”
This
procedure may be used if the AWA works properly on any other motors
and coils connected to it. It is certainly NOT going to fix a broken
down or out of calibration machine. This procedure should only be
performed to correct this SPECIFIC problem.
The
AWA has a noise measurement algorithm in it, which is designed to
allow in situ detection of free - wheeling motors, with fans and pumps
connected. It is possible to confuse it in certain circumstances.
Workaround:
There
are two methods available to alleviate the problem
1) Edit the C:\Winnt\Awa.ini file, can be done in the field. If
this procedure is followed properly, will not alter the calibration in
any way.
2) Calibrate the unit, which will edit the C:\Winnt\Awa.ini file,
should only be performed by authorized technical personnel. Not
recommended for field use.
|
|||||||||||
Item
1:
Close
the AWA application
Single
RIGHT click “My Computer” – Explore
Browse
to C:\Winnt\Awa.ini
Single
RIGHT click Awa.ini – Copy – Paste into same folder. Will now add
a file called Copy of Awa.ini. This file can be used for a backup if
you mess up
Double
LEFT click Awa.ini
Verify
it opens in Notepad
The
last line in the Awa.ini file shows: MaxPercentADC=10
*Change
this value with notepad to 30 (Now looks like: MaxPercentADC=30)
File
– Save
Launch
the AWA application, and re-run the test.
Item
2:
Should
only be performed by authorized technical personnel, and is not
recommended for field use.
*Baker
Instrument Company recommended. Slightly smaller values between 10 and
29 may work, or larger values such as 40 may work, but larger values
will excessively reduce the sensitivity of the equipment.
|
||||||||||||
|
||||||||||||
![]() |